Re: [MV] Electrical question

From: Randy Orpe (sgtorpe@sierratel.com)
Date: Sat Oct 14 2000 - 20:58:27 PDT


Figure out the power requirements of all the stuff you are going to plug
into the Generator set and then get a set that exceeds your load
requirements by at least 10%. OR you get a smaller gen set and load shift
 run only part of your equipment at the same time ) I can run a house as
just described on a 3KW but to run it all at once I would need a 5KW.
Remember that diesel gen sets need to be run above 50% load most of the time
in order to be efficient and to prevent mechanical problems ( like injector
slobber ).

Randy

----- Original Message -----
From: <DDoyle9570@aol.com>
To: Military Vehicles Mailing List <mil-veh@mil-veh.org>
Sent: Saturday, October 14, 2000 7:06 PM
Subject: [MV] Electrical question

> I hope to pick up tomorrow the air conditioner unit that is correct for my
> M292A2 expansible van.
> The A/C is 208 volt 3 phase, 60 cycle. It has a 28.5 amp requirement.
> My question is what size generator will be needed to power this? What
size
> would I need to also power the few (8 two bulb fixtures) fluorescent
lights
> in the van body?
>
> Also, does anyone have any experience installing these? Which goes in
first,
> the A/C or the heaters?
>
> Any help appreciated.
>
> Thanks,
> David Doyle
>